Дата обновления:

Square D CE6GQA BDA34125Y

Ключевые характеристики BDA34125Y

Серия
BDA34125Y
Item
Circuit Breaker
Ac Voltage Rating
277/480V AC

Преимущества работы с Raxwell

  • Доставляем во все регионы России
  • Берём всё под ключ — от подбора до доставки
  • Быстро считаем стоимость и соблюдаем сроки
  • Всегда на связи и сопровождаем на каждом этапе
Ключевые характеристики
Серия
BDA34125Y
Item
Circuit Breaker
Ac Voltage Rating
277/480V AC
Ambient Air Temp. For Operation
-13°F to +158°F
Ambient Air Temp. For Storage
-58°F to +185°F
Amps
125A
Awg Gauge
14 AWG to 2/0 AWG
Breaking Capacity
25 kA 208Y/120V AC 50/60 Hz UL 489, 25 kA 240V AC 50/60 Hz UL 489, 18 kA 480/277V AC 50/60 Hz UL 489, 18 kA 480V AC 50/60 Hz UL 489, 14 kA 600Y/347V AC 50/60 Hz UL 489, 10 kA 250V DC UL 489
Breaking Capacity Code
D
Circuit Breaker Actuator
Toggle
Circuit Breaker Application
HACR Rated
Circuit Breaker Mounting Style
I-Line
Circuit Breaker Type
Standard
Color
Gray
Component Type
Circuit Breaker
Connection Pitch
1.06"
Continuous Amps Rating
80%
Control Type
Toggle
Dc Voltage Rating
Not Rated
Depth
3.5"
Device Application
Distribution
Electrical Connection
I-Line Connection, Line, Lugs, Load
Electrical Durability
10000 Cycles
For Use With
Electrical Distribution Equipment, Industrial Control Panels
Frame Size
125A, BD
Frame Type
BDA
Height
5.39"
Ik Degree Of Protection
IK07
Instantaneous Trip
Fixed
Ip Degree Of Protection
IP40
Line Rated Amps
125A
Local Signalling
Presence Of Auxiliary Contacts Flag Green
Max. Air Rating
25 kA At 277/408V AC
Max. Operating Temp.
158°F
Max. Wire Size
2 AWG
Mechanical Durability
20000 Cycles
Min. Operating Temp.
-13°F
Min. Wire Size
14 AWG
Mounting Height
4.5"
Mounting Mode
I Line
Network Frequency
50/60 Hz
No. Of 9 Mm Pitches
9
No. Of Poles
3
Number Of Poles
3
Number Of Slots
3
Operating Altitude
0 ft. to 6561.68 ft. Without Derating, 5000m With Derating
Phase
Three
Phase Connection
ABC
Pollution Degree
3 IEC 60947-1
Power Wire Stripping Length
0.8"
Quality Labels
ce.png
Quantity Per Set
Set of 1
Rated Impulse Withstand Voltage
8 kV
Rated Insulation Voltage
800V
Rated Operational Voltage
525V
Rated Service Breaking Capacity
25 kA @ 220-240V AC @ 50/60 Hz, 14 kA @ 500-525V AC @ 50/60 Hz, 18 kA @ 380-415V AC @ 50/60 Hz, 18 kA @ 440V AC @ 50/60 Hz
Returnability
Yes
Suitability For Isolation
Yes, IEC 60947-2
Terminal Connection
Al Mechanical Lug Off End, I-Line On End
Tightening Torque
31.9 lbf.in. to 38.9 lbf.in. @ 0.004 sq. in. to 0.009 sq. in. @ 14 AWG to 10 AWG, 44.3 lbf.in. to 54.9 lbf.in. @ 0.02 sq. in. to 0.1 sq. in. @ 8 AWG to 2/0 AWG
Trip Type
Thermal Magnetic
Trip Unit Technology
Thermal-Magnetic
Utilisation Category
Category A
Voltage
600V
Voltage Type
AC
Width
3.19"
Standards
CSA C22.2 NO 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB1, NMX J-266, UL 489
Техническое резюме
SQUARE D BDA34125Y PowerPact B Series circuit breaker designed to offer protection by cutting off the electrical supply in the event of short-circuit and overload occurrences, Type B design allows tripping at faulty currents rated 3 to 5 times the preset amperage values; ideal for lighting, solar, telecom and railway signalling applications, Features a fixed instantaneous, thermal-magnetic trip unit adjusted to a pre-determined overcurrent value (.05 - 0.5 sec) for accentuating the control toggle when exposed to current surges, NEMA-rated, UL-listed and CSA-certified, SQUARE D BDA34125Y PowerPact B Series circuit breaker designed to offer protection by cutting off the electrical supply in the event of short-circuit and overload occurrences, Type B design allows tripping at faulty currents rated 3 to 5 times the preset amperage values; ideal for lighting, solar, telecom and railway signalling applications, Features a fixed instantaneous, thermal-magnetic trip unit adjusted to a pre-determined overcurrent value (.05 - 0.5 sec) for accentuating the control toggle when exposed to current surges, NEMA-rated, UL-listed and CSA-certified

Square D

Square D — автоматические выключатели, контакторы, пускатели, реле, трансформаторы управления и преобразователи частоты для силовых цепей и управления двигателями. Исполнения различаются током, напряжением и числом полюсов.