Square D CE6HWK BGA36090
Ключевые характеристики BGA36090
- Серия
- BGA36090
- Item
- Circuit Breaker
- Ac Voltage Rating
- 525V AC
Преимущества работы с Raxwell
- Доставляем во все регионы России
- Берём всё под ключ — от подбора до доставки
- Быстро считаем стоимость и соблюдаем сроки
- Всегда на связи и сопровождаем на каждом этапе
Ключевые характеристики
- Серия
- BGA36090
- Item
- Circuit Breaker
- Ac Voltage Rating
- 525V AC
- Ambient Air Temp. For Operation
- -13°F to +158°F
- Ambient Air Temp. For Storage
- -58°F to +185°F
- Amps
- 90A
- Awg Gauge
- 14 AWG to 2/0 AWG
- Breaking Capacity
- 65 kA 208Y/120V AC 50/60 Hz UL 489, 65 kA 240V AC 50/60 Hz UL 489, 35 kA 480/277V AC 50/60 Hz UL 489, 35 kA 480V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489, 18 kA 600Y/347V AC 50/60 Hz UL 489
- Breaking Capacity Code
- G
- Circuit Breaker Actuator
- Toggle
- Circuit Breaker Application
- HACR Rated
- Circuit Breaker Mounting Style
- I-Line
- Circuit Breaker Type
- Standard
- Color
- Gray
- Component Type
- Circuit Breaker
- Connection Pitch
- 1.06"
- Continuous Amps Rating
- 80%
- Control Type
- Toggle
- Dc Voltage Rating
- Not Rated
- Depth
- 3.5"
- Device Application
- Distribution
- Electrical Connection
- I-Line Connection, Line, Lugs, Load
- Electrical Durability
- 10000 Cycles
- For Use With
- Electrical Distribution Equipment, Industrial Control Panels
- Frame Size
- 125A, BG
- Frame Type
- BGA
- Height
- 5.39"
- Ik Degree Of Protection
- IK07
- Instantaneous Trip
- Fixed
- Ip Degree Of Protection
- IP40
- Line Rated Amps
- 90A
- Local Signalling
- Presence Of Auxiliary Contacts Flag Green
- Max. Air Rating
- 100 kA At 240V AC
- Max. Operating Temp.
- 158°F
- Max. Wire Size
- 2 AWG
- Mechanical Durability
- 20000 Cycles
- Min. Operating Temp.
- -13°F
- Min. Wire Size
- 14 AWG
- Mounting Height
- 4.5"
- Mounting Mode
- I Line
- Network Frequency
- 50/60 Hz
- No. Of 9 Mm Pitches
- 9
- No. Of Poles
- 3
- Number Of Poles
- 3
- Number Of Slots
- 3
- Operating Altitude
- 0 ft. to 6561.68 ft. Without Derating, 5000m With Derating
- Phase
- Three
- Phase Connection
- ABC
- Pollution Degree
- 3 IEC 60947-1
- Power Wire Stripping Length
- 0.8"
- Quality Labels
- ce.png
- Quantity Per Set
- Set of 1
- Rated Impulse Withstand Voltage
- 8 kV
- Rated Insulation Voltage
- 800V
- Rated Operational Voltage
- 525V
- Rated Service Breaking Capacity
- 65 kA @ 220-240V AC @ 50/60 Hz, 18 kA @ 500-525V AC @ 50/60 Hz, 35 kA @ 380-415V AC @ 50/60 Hz, 35 kA @ 440V AC @ 50/60 Hz
- Returnability
- Yes
- Suitability For Isolation
- Yes, IEC 60947-2
- Terminal Connection
- Al Mechanical Lug Off End, I-Line On End
- Tightening Torque
- 31.9 lbf.in. to 38.9 lbf.in. @ 0.004 sq. in. to 0.009 sq. in. @ 14 AWG to 10 AWG, 44.3 lbf.in. to 54.9 lbf.in. @ 0.02 sq. in. to 0.1 sq. in. @ 8 AWG to 2/0 AWG
- Trip Type
- Thermal Magnetic
- Trip Unit Technology
- Thermal-Magnetic
- Utilisation Category
- Category A
- Voltage
- 600V
- Voltage Type
- AC
- Width
- 3.19"
- Standards
- CSA C22.2 NO 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB1, NMX J-266, UL 489
Техническое резюме
Square D BGA36090 circuit breaker designed to provide overcurrent protection by limiting the current flow, Thermal magnetic trip unit provide both long time and instantaneous current limiting functions, at 90A rated current, Unique I-Line style plug-in facility comfortably mounts into all kinds of panelboards and switchboards for fast installation and repair, Square D BGA36090 circuit breaker designed to provide overcurrent protection by limiting the current flow, Thermal magnetic trip unit provide both long time and instantaneous current limiting functions, at 90A rated current, Unique I-Line style plug-in facility comfortably mounts into all kinds of panelboards and switchboards for fast installation and repair
Документация
Square D
Выключатель подбирают по номинальному току, числу полюсов и напряжению, контактор — по току и напряжению катушки. В запросе нужен полный номер с шильдика; если он не читается, приложите фото.
Подробнее о бренде