Дата обновления:

Square D CE6JNM HJL36030M71

Ключевые характеристики HJL36030M71

Серия
HJL36030M71
Item
Circuit Breaker
Ambient Air Temp. For Operation
-13°F to +158°F

Преимущества работы с Raxwell

  • Доставляем во все регионы России
  • Берём всё под ключ — от подбора до доставки
  • Быстро считаем стоимость и соблюдаем сроки
  • Всегда на связи и сопровождаем на каждом этапе
Ключевые характеристики
Серия
HJL36030M71
Item
Circuit Breaker
Ambient Air Temp. For Operation
-13°F to +158°F
Ambient Air Temp. For Storage
-58°F to +185°F
Amps
30A
Awg Gauge
14 AWG to 3/0 AWG
Breaking Capacity
100 kA 240V AC 50/60 Hz UL 489, 65 kA 480V AC 50/60 Hz UL 489, 25 kA 600V AC 50/60 Hz UL 489, 20 kA 250V DC UL 489
Breaking Capacity Code
J
Color
Black
Communication Interface
Modbus, Ethernet
Component Type
Motor Circuit Protector
Continuous Amps Rating
80%
Control Type
Toggle
Conventional Free Air Thermal Current
1.5-25A
Depth
3.4"
Device Application
Distribution
Electrical Connection
Lugs, Line, Load
Frame Type
HJL
Height
6 2/5"
Ip Degree Of Protection
IP40
Line Rated Amps
30A
Magnetic Tripping Amps
9-325A
Mounting Mode
Unit Mount Lug
Mounting Support
Lug
Network Frequency
50/60 Hz
No. Of Poles
3
Number Of Poles
3
Number Of Slots
5
Operating Altitude
0 ft. to 6561.68 ft. Without Derating, 5000m With Derating
Pollution Degree
3 IEC 60947-1
Power Wire Stripping Length
0.6"
Quality Labels
ce.png
Quantity Per Set
1
Rated Impulse Withstand Voltage
8 kV
Rated Insulation Voltage
750V
Rated Operational Voltage
690V
Rated Service Breaking Capacity
65 kA @ 220/240V AC @ 50/60 Hz, 35 kA @ 380/440/415V AC @ 50/60 Hz, 18 kA @ 500/525V AC @ 50/60 Hz, 20 kA @ 250V DC, 20 kA @ 500V DC
Returnability
Yes
Suitability For Isolation
Yes, IEC 60947-2
Tightening Torque
44.3 lbf.in. @ 0.004 sq. in. to 0.009 sq. in. @ 14 AWG to 10 AWG, 123.9 lbf.in. @ 0.02 sq. in. to 0.1 sq. in. @ 8 AWG to 3/0 AWG
Trip Unit Technology
Thermal-Magnetic
Utilisation Category
Category A
Voltage
600V
Voltage Type
AC
Width
4.09"
Warranty
18 Months
Техническое резюме
Square D HJL36030M71 circuit breaker designed to protect MCP motor circuits; suitable for reverse-feed applications, Electronic trip mechanism to provide instantaneous current limiting function with an adjustable magnetic trip range of 1125 - 2250 A, Features line- and load-side lug terminals with feed-thru connection for better wiring configuration, Accommodates aluminium or copper wire sizes within a range of 14 - 3/0 AWG, Square D HJL36030M71 circuit breaker designed to protect MCP motor circuits; suitable for reverse-feed applications, Electronic trip mechanism to provide instantaneous current limiting function with an adjustable magnetic trip range of 1125 - 2250 A, Features line- and load-side lug terminals with feed-thru connection for better wiring configuration, Accommodates aluminium or copper wire sizes within a range of 14 - 3/0 AWG

Square D

Марка основана в Детройте в 1902 году, с 1991 года принадлежит Schneider Electric. Номера бывают числовыми (462994), длинными числовыми (0320226101) и смешанными (10S40FSS); один знак меняет исполнение.
Подробнее о бренде